configurations: harma_mb_vr_infineon: add hysteresis
The hysteresis value is set to 2% of the trigger threshold to ensure more precise triggering of assert and deassert for sensors like a 12V sensor
configurations: harma_mb_vr_infineon: add hysteresis
The hysteresis value is set to 2% of the trigger threshold to ensure more precise triggering of assert and deassert for sensors like a 12V sensor. For example, with normal readings and thresholds at ±10% (10.8V to 13.2V), the default value of 2.55 is too large for this range.
Change-Id: Ic3b6db086068c84e1c09cb4819f80bbba3a3f542 Signed-off-by: Daniel Hsu <Daniel-Hsu@quantatw.com>