99b5f613 |
| 12-Dec-2024 |
Daniel Hsu <Daniel-Hsu@quantatw.com> |
configurations: minerva_pdb_hsc_xdp: add hysteresis
The hysteresis value is set to 2% of the trigger threshold to ensure more precise triggering of assert and deassert for sensors like a 12V sensor.
configurations: minerva_pdb_hsc_xdp: add hysteresis
The hysteresis value is set to 2% of the trigger threshold to ensure more precise triggering of assert and deassert for sensors like a 12V sensor. For example, with normal readings and thresholds at ±10% (10.8V to 13.2V), the default value of 2.55 is too large for this range.
Change-Id: Ib612861a4ad70aa669b5fb8dc90a9ccf0a231c8e Signed-off-by: Daniel Hsu <Daniel-Hsu@quantatw.com>
show more ...
|