Revision Date Author Comments
# 7ee0961d 16-Dec-2024 Yang Chen <yang.chen@quantatw.com>

configurations: minerva_cmm: add hysteresis

The hysteresis value is set to 2% of the trigger threshold
to ensure more precise triggering of assert and deassert for
sensors like a 12V sensor. For exa

configurations: minerva_cmm: add hysteresis

The hysteresis value is set to 2% of the trigger threshold
to ensure more precise triggering of assert and deassert for
sensors like a 12V sensor. For example, with normal readings
and thresholds at ±10% (10.8V to 13.2V), the default value of
2.55 is too large for this range.

Change-Id: Ifb0597181725ec19fdff4082f27e7cc553bac512
Signed-off-by: Yang Chen <yang.chen@quantatw.com>