Lines Matching +full:temperature +full:- +full:mode
19 -----------
22 The chip has one on-chip and one remote temperature sensor and one pwm fan
29 temp1_input ro on-chip temperature
37 temp2_input ro remote temperature
53 pwm1_enable rw regulator mode, 1=open loop, 2=fan controlled
54 by remote temperature, 3=fan controlled by
55 combination of the on-chip temperature and
56 remote-sensor temperature,
59 temperature channels.
60 pwm1_auto_point2_pwm rw This value is shared for both temperature
63 temperature channels.
66 which is rw. Below this temperature fan stops.
67 temp1_auto_point2_temp rw The low-temperature limit of the proportional
68 range. Below this temperature
73 temp1_auto_point3_temp rw Above this temperature fan runs at maximum
81 it defines the passive cooling temperature.
82 Below this temperature the fan stops in
83 the closed loop mode.
84 temp2_auto_point2_temp rw The low-temperature limit of the proportional
85 range. Below this temperature
90 temp2_auto_point3_temp rw Above this temperature fan runs at maximum
99 -----------------
107 - init=1,
108 - pwminv: 0 default pwm output, 1 inverts pwm output.