Searched hist:"4 c94ed9f" (Results 1 – 1 of 1) sorted by relevance

/openbmc/entity-manager/configurations/
H A Dmori_motherboard.json4c94ed9f Tue Jul 25 15:06:03 CDT 2023 Jonico Eustaquio <jonico.eustaquio@fii-na.com> mori_motherboard: Add 5s timeout to ext sensor and thresh to psu0_temp

Add 5s timeout for THERMAL_ZONE0_T external sensor so that its reading
can go to NaN and cause fans to go to fail safe mode if the sensor is
not driven.

An upper non-critical threshold of 105C and upper critical threshold of
120C has been added to the psu0_temp sensor.

Change-Id: Iea3a81200fa7e38d5b19e8d3d9be7505be2a0cf2
Signed-off-by: Jonico Eustaquio <jonico.eustaquio@fii-na.com>