/openbmc/openbmc/meta-ampere/meta-mitchell/recipes-phosphor/fans/phosphor-fan/
H A Dpresence.json2a98e334 Mon Jun 13 23:31:58 CDT 2022 Chau Ly <chaul@amperecomputing.com> meta-ampere: mtmitchell: support automatic FAN control

Implement automatic FAN control table provided by ODM.
The FAN console service will set Fans to 100% duty cycle in below cases:
- Lacking any of the fans
- Any of the fan tachs is non-functional (not running at the desired
target)
- Any of the controlling sensors is non-functional (except for pluggable
device sensors)

Change-Id: Id7069e0731cb330a9d39c9334d4d20ad4179e9e5
Signed-off-by: Chau Ly <chaul@amperecomputing.com>
H A Devents.json2a98e334 Mon Jun 13 23:31:58 CDT 2022 Chau Ly <chaul@amperecomputing.com> meta-ampere: mtmitchell: support automatic FAN control

Implement automatic FAN control table provided by ODM.
The FAN console service will set Fans to 100% duty cycle in below cases:
- Lacking any of the fans
- Any of the fan tachs is non-functional (not running at the desired
target)
- Any of the controlling sensors is non-functional (except for pluggable
device sensors)

Change-Id: Id7069e0731cb330a9d39c9334d4d20ad4179e9e5
Signed-off-by: Chau Ly <chaul@amperecomputing.com>
H A Dfans.json2a98e334 Mon Jun 13 23:31:58 CDT 2022 Chau Ly <chaul@amperecomputing.com> meta-ampere: mtmitchell: support automatic FAN control

Implement automatic FAN control table provided by ODM.
The FAN console service will set Fans to 100% duty cycle in below cases:
- Lacking any of the fans
- Any of the fan tachs is non-functional (not running at the desired
target)
- Any of the controlling sensors is non-functional (except for pluggable
device sensors)

Change-Id: Id7069e0731cb330a9d39c9334d4d20ad4179e9e5
Signed-off-by: Chau Ly <chaul@amperecomputing.com>
H A Dphosphor-fan-control@.service2a98e334 Mon Jun 13 23:31:58 CDT 2022 Chau Ly <chaul@amperecomputing.com> meta-ampere: mtmitchell: support automatic FAN control

Implement automatic FAN control table provided by ODM.
The FAN console service will set Fans to 100% duty cycle in below cases:
- Lacking any of the fans
- Any of the fan tachs is non-functional (not running at the desired
target)
- Any of the controlling sensors is non-functional (except for pluggable
device sensors)

Change-Id: Id7069e0731cb330a9d39c9334d4d20ad4179e9e5
Signed-off-by: Chau Ly <chaul@amperecomputing.com>
H A Dphosphor-fan-presence-tach@.service2a98e334 Mon Jun 13 23:31:58 CDT 2022 Chau Ly <chaul@amperecomputing.com> meta-ampere: mtmitchell: support automatic FAN control

Implement automatic FAN control table provided by ODM.
The FAN console service will set Fans to 100% duty cycle in below cases:
- Lacking any of the fans
- Any of the fan tachs is non-functional (not running at the desired
target)
- Any of the controlling sensors is non-functional (except for pluggable
device sensors)

Change-Id: Id7069e0731cb330a9d39c9334d4d20ad4179e9e5
Signed-off-by: Chau Ly <chaul@amperecomputing.com>
H A Dzones.json2a98e334 Mon Jun 13 23:31:58 CDT 2022 Chau Ly <chaul@amperecomputing.com> meta-ampere: mtmitchell: support automatic FAN control

Implement automatic FAN control table provided by ODM.
The FAN console service will set Fans to 100% duty cycle in below cases:
- Lacking any of the fans
- Any of the fan tachs is non-functional (not running at the desired
target)
- Any of the controlling sensors is non-functional (except for pluggable
device sensors)

Change-Id: Id7069e0731cb330a9d39c9334d4d20ad4179e9e5
Signed-off-by: Chau Ly <chaul@amperecomputing.com>
H A Dmonitor.json2a98e334 Mon Jun 13 23:31:58 CDT 2022 Chau Ly <chaul@amperecomputing.com> meta-ampere: mtmitchell: support automatic FAN control

Implement automatic FAN control table provided by ODM.
The FAN console service will set Fans to 100% duty cycle in below cases:
- Lacking any of the fans
- Any of the fan tachs is non-functional (not running at the desired
target)
- Any of the controlling sensors is non-functional (except for pluggable
device sensors)

Change-Id: Id7069e0731cb330a9d39c9334d4d20ad4179e9e5
Signed-off-by: Chau Ly <chaul@amperecomputing.com>
H A Dphosphor-fan-monitor@.service2a98e334 Mon Jun 13 23:31:58 CDT 2022 Chau Ly <chaul@amperecomputing.com> meta-ampere: mtmitchell: support automatic FAN control

Implement automatic FAN control table provided by ODM.
The FAN console service will set Fans to 100% duty cycle in below cases:
- Lacking any of the fans
- Any of the fan tachs is non-functional (not running at the desired
target)
- Any of the controlling sensors is non-functional (except for pluggable
device sensors)

Change-Id: Id7069e0731cb330a9d39c9334d4d20ad4179e9e5
Signed-off-by: Chau Ly <chaul@amperecomputing.com>
/openbmc/openbmc/meta-ampere/meta-common/recipes-phosphor/fans/
H A Dphosphor-fan_%.bbappend2a98e334 Mon Jun 13 23:31:58 CDT 2022 Chau Ly <chaul@amperecomputing.com> meta-ampere: mtmitchell: support automatic FAN control

Implement automatic FAN control table provided by ODM.
The FAN console service will set Fans to 100% duty cycle in below cases:
- Lacking any of the fans
- Any of the fan tachs is non-functional (not running at the desired
target)
- Any of the controlling sensors is non-functional (except for pluggable
device sensors)

Change-Id: Id7069e0731cb330a9d39c9334d4d20ad4179e9e5
Signed-off-by: Chau Ly <chaul@amperecomputing.com>
/openbmc/openbmc/meta-ampere/meta-mitchell/recipes-phosphor/fans/
H A Dphosphor-fan_%.bbappend2a98e334 Mon Jun 13 23:31:58 CDT 2022 Chau Ly <chaul@amperecomputing.com> meta-ampere: mtmitchell: support automatic FAN control

Implement automatic FAN control table provided by ODM.
The FAN console service will set Fans to 100% duty cycle in below cases:
- Lacking any of the fans
- Any of the fan tachs is non-functional (not running at the desired
target)
- Any of the controlling sensors is non-functional (except for pluggable
device sensors)

Change-Id: Id7069e0731cb330a9d39c9334d4d20ad4179e9e5
Signed-off-by: Chau Ly <chaul@amperecomputing.com>