/** * Copyright 2017 Google Inc. * * Licensed under the Apache License, Version 2.0 (the "License"); * you may not use this file except in compliance with the License. * You may obtain a copy of the License at * * http://www.apache.org/licenses/LICENSE-2.0 * * Unless required by applicable law or agreed to in writing, software * distributed under the License is distributed on an "AS IS" BASIS, * WITHOUT WARRANTIES OR CONDITIONS OF ANY KIND, either express or implied. * See the License for the specific language governing permissions and * limitations under the License. */ #include "pidloop.hpp" #include "pid/pidcontroller.hpp" #include "pid/tuning.hpp" #include "sensors/sensor.hpp" #include #include #include #include #include #include static void processThermals(PIDZone* zone) { // Get the latest margins. zone->updateSensors(); // Zero out the set point goals. zone->clearSetPoints(); zone->clearRPMCeilings(); // Run the margin PIDs. zone->processThermals(); // Get the maximum RPM setpoint. zone->determineMaxSetPointRequest(); } void pidControlLoop(PIDZone* zone, boost::asio::steady_timer& timer, bool first, int ms100cnt) { if (first) { if (loggingEnabled) { zone->initializeLog(); } zone->initializeCache(); processThermals(zone); } timer.expires_after(std::chrono::milliseconds(100)); timer.async_wait( [zone, &timer, ms100cnt](const boost::system::error_code& ec) mutable { if (ec == boost::asio::error::operation_aborted) { return; // timer being canceled, stop loop } /* * This should sleep on the conditional wait for the listen thread * to tell us it's in sync. But then we also need a timeout option * in case phosphor-hwmon is down, we can go into some weird failure * more. * * Another approach would be to start all sensors in worst-case * values, and fail-safe mode and then clear out of fail-safe mode * once we start getting values. Which I think it is a solid * approach. * * For now this runs before it necessarily has any sensor values. * For the host sensors they start out in fail-safe mode. For the * fans, they start out as 0 as input and then are adjusted once * they have values. * * If a fan has failed, it's value will be whatever we're told or * however we retrieve it. This program disregards fan values of 0, * so any code providing a fan speed can set to 0 on failure and * that fan value will be effectively ignored. The PID algorithm * will be unhappy but nothing bad will happen. * * TODO(venture): If the fan value is 0 should that loop just be * skipped? Right now, a 0 value is ignored in * FanController::inputProc() */ // Check if we should just go back to sleep. if (zone->getManualMode()) { pidControlLoop(zone, timer, false, ms100cnt); return; } // Get the latest fan speeds. zone->updateFanTelemetry(); if (10 <= ms100cnt) { ms100cnt = 0; processThermals(zone); } // Run the fan PIDs every iteration. zone->processFans(); if (loggingEnabled) { zone->getLogHandle() << "," << zone->getFailSafeMode(); zone->getLogHandle() << std::endl; } ms100cnt += 1; pidControlLoop(zone, timer, false, ms100cnt); }); }