description: > Implement to emit D-Bus signal for PLDM Event Messages. PLDM Event Messages are PLDM monitoring and control messages that are used by a PLDM terminus to synchronously or asynchronously report PLDM events to a central party called the PLDM Event Receiver. When the PLDM daemon receives a sensorEvent of type stateSensorState, it emits the StateSensorEvent signal. This signal would be used by PLDM Requester apps on the BMC, which will rely on this signal to determine state changes on a connected PLDM entity. More information about PLDM Event Messages can be found at DSP0248 version 1.2.0 section 13. signals: - name: StateSensorEvent description: > Signal indicating that a state sensor change EventMessage is received. More information about properties can be found at DSP0248 version 1.2.0 table 19. properties: - name: TID type: byte description: > A terminus id. - name: sensorID type: uint16 description: > The sensorID is the value that is used in PDRs and PLDM sensor access commands to identify and access a particular sensor within a terminus. - name: sensorOffset type: byte description: > Identifies which state sensor within a composite state sensor the event is being returned for. - name: eventState type: byte description: > The event state value from the state change that triggered the event message. - name: previousEventState type: byte description: > The event state value for the state from which the present event state was entered.