55 The trigger `init.get_properties` will, on fan control startup, read the Present
60 The trigger `signal.properties_changed` will watch for changes on the Present
64 The `count_state_before_target` action will look at the object cache value of
66 15000 when one or more of them is false. Otherwise, it will clear its fan target
88 The actions and triggers defined with this group will look at this D-Bus
93 The actions and triggers defined with this group will look at this D-Bus
105 will run.
138 member. When the signal occurs, the new property value will be added to or
143 signal occurs, the interface and its properties will be added to the object
148 the signal occurs, the interface and properties will be removed from the
153 each group member. When the signal occurs, the service owned state will be
184 Optional, if set to true, will update the D-Bus properties from the configured
409 for 3 seconds, a floor hold will be requested with a value of 18000. Otherwise,
410 the floor hold will be released (if it was previously requested).
429 false, a target hold will be requested with a value of 18000. Otherwise, the
430 hold will be released (if it was previously requested).
477 The above config will use the maximum value of the 'ambient temp' group as the
479 will be used when the key group has a max value of less than 25.
481 It will then traverse the contained floors arrays, keeping track of the highest
482 valid floor value it finds. If it doesn't find any valid floor values, it will
489 At the end of the analysis, a floor hold will be set with the final floor value.
540 The above config will set a target hold of 18000 when the service associated
548 it will either revert to temperature control or activate the next-highest target
561 The above config will lock all fans in the fans array at a target of 10000 when
624 The above config will set the requested target base to the maximum Target
644 The above config will first find the max of its groups property values, subtract
652 the mapping of all groups will be set to the zone's target.
677 The above JSON will cause the action to read the property specified in the group
679 value will be checked against "neg_hysteresis" and "pos_hysteresis" to decide if
682 group will be mapped to the "map" to get the output "target". Each configured
683 event using this action will be provided with a key in a static map to store its
684 mapping result. The static map will be shared across the events of this action.
685 Therefore, the updated "target" value derived from "zone0_ambient" will be
688 maximum value from it will be used to set to the Zone's target.
695 When all groups have a configured value to compare against, that will be
732 Then a oneshot timer of 5000000us will be started when every member of the fan
733 inventory group has a value of true. Otherwise, the timer will be stopped if
746 Then the timer will be started when any service providing a group member isn't
747 owned (on D-Bus). Otherwise, it will stop the timer if it's running.
778 The above config will make the GetManagedObjects call on all services that own
780 cache. After that, it will call the `set_net_increase_target` action using the
804 `default_value` field supplied, then that will be returned if the argument is